981_main
981_group
981_main
981_group
BECK

Pressure Transmitter 981

Permissible Environmental ConditionsStorage and operating temperature –20°C to +85°C
Media temperature 0 to 85°C
Humidity max. 95% rH., non-condensing
Membrane MaterialNBR, Silicone, FKM, EPDM
Response Time500 ms
Supply Voltage10 ... 30 VDC 2-wire
18 ... 30 VDC 3-wire
Supply Current≤ 21 mA 2-wire
≤ 50 mA 3-wire
Output Signal4 - 20 mA 2-wire
0 - 10 VDC 3-wire
LoadMax. 500 Ω at 24 VDC 2-wire
Min. 1 kΩ 3-wire
Electrical ConnectionM12 socket, 4 poles, A-coded
Protection ClassIP65 according to EN 60529
ConformityRoHS Directive, EMC Directive
Accuracy SpecificationsAccording to EN 60770, reference temperature: 23 °C
Mounting PositionMounting in any position
WeightApprox. 100 gr
DatasheetsTechnical Datasheet
Login to see prices In Stock Sold out

Pressure transmitter for monitoring overpressure and negative pressure, for liquid and gaseous, as well as aggressive media. The pressure measurement is relative to the atmospheric pressure.

.