Monitor two separate leak detection zones

Combine the LeakPro® LD2C controller with LDC-B sensing cable to monitor conductive liquid leaks across two independent areas, with separate alerts for liquid contact and cable breaks.

PVL supplies ICON Process Controls instrumentation with technical support for cable selection, layout and alarm integration.

Download system datasheet (PDF)Enquire about your system

LeakPro LD2C two-channel controller and LDC-B conductive liquid sensing cable
LD2C controller with compatible LDC-B sensing cable. Cable sold separately.
2 channels

Independent monitoring of two cable runs

500 m

Maximum sensing cable length per channel

RS485

Modbus RTU plus two independent relay outputs

How the system works

Install LDC-B cable along the areas to be monitored. Conductive liquid bridging the sensing wires triggers a leak alarm on that channel. A cut or disconnected sensing cable produces a separate break alert, helping operators recognise an interruption in monitoring coverage.

The front colour TFT display and Power, Alarm and Break indicators show channel status locally. Relay outputs and RS485 Modbus RTU provide connections to external alarms, a PLC or a building management system.

Detection coverage
The LD2C reports which channel is affected. Each channel can monitor up to 500 m of LDC-B cable. Leak position within the cable run requires a distance-locating system.

LD2C controller

  • Two independent sensing channels
  • Separate leak and cable-break notifications
  • Adjustable sensitivity and alarm delays
  • Colour TFT display with status LEDs
  • Two 3 A relay outputs and RS485 Modbus RTU
  • NEMA 4X enclosure

LDC-B sensing cable

  • Two-wire sensing for conductive liquids
  • Detection along the installed sensing cable
  • Chemical-resistant polyethylene jacket
  • Pre-wired M12 connectors shown in the datasheet
  • Selectable cable lengths, supplied separately

The LD2C is designed specifically for LDC-B cable. PVL can help confirm the liquid, cable lengths and installation requirements.

Typical applications

  • Data centres, server rooms and raised-floor areas
  • Mechanical rooms, HVAC and chiller installations
  • Water storage areas
  • Pump stations and process skids
  • Equipment perimeters and pipe routes

Technical specifications

Detection channels 2 independent channels
Compatible sensing cable LeakPro® LDC-B
Detection medium Conductive liquids compatible with the sensing cable
Sensing capacity Up to 500 m per channel
Supply voltage 9–30 VDC
Maximum power 1.5 W, as stated in ICON’s datasheet
Display Colour TFT with Power, Alarm and Break indicator LEDs
Outputs 2 independent relays and RS485
Relay rating 3 A at 30 VDC or 250 VAC
Communication Modbus RTU over 2-wire RS485
Factory communication settings 9600 bps; device address 5
Operating temperature −20 to +80 °C
Operating humidity 5–95% RH, non-condensing
Controller enclosure NEMA 4X

Datasheet and installation information

The official seven-page ICON datasheet includes the controller specifications, LDC-B sensing principle, application example, wiring diagram, commissioning guidance and Modbus RTU information.

Download LD2C system datasheet (PDF)

ICON Process Controls document 26-1223.

Discuss your application with a PVL engineer

Tell us the liquid you need to detect, the length of each cable run and your alarm, PLC or BMS requirements. We can help select the controller and sensing cable and provide a quotation.

Email PVL technical salesCall 01892 664499